Lithium Battery Aging Rack Fire Warning Scheme

 

  • Background

                Before some lithium batteries leave the factory, lithium battery manufacturers will put them on the aging rack for aging test. Lithium batteries come in different shapes and sizes. During the aging process, some batteries with abnormal quality will catch fire. For the fire of a single battery, the smoke in the aging room cannot be detected at all. When a single fire battery ignites the normal battery next to it, the smoke will be detected, and the fire will be difficult to extinguish by this time.

 

  • Functional Requirements

              Before the lithium battery catches fire, an abnormality of a single lithium battery is detected, and the abnormal single lithium battery is dealt with to avoid the occurrence of fire.

 

  • Function Realization

                Before a single lithium battery catches fire, the temperature rises and produces peculiar smell. When a single lithium battery catches fire, it will produce light smoke (which cannot be detected by the smoke sensor). In view of the above situation, select the appropriate sensor to detect the abnormality of the lithium battery. When the sensor finds an abnormality, it will be transmitted wirelessly and reported to the corresponding management personnel, and the corresponding management personnel will take measures.

 

  • Temperature Monitoring

                Lay a temperature measuring resistor under each battery, place a temperature-reading collector on each row of aging racks, collect the temperature of each battery point in real time and upload it to the management platform. When the temperature is abnormal, it will alarm immediately.

 

  • Air Quality Monitoring

                When the temperature of a single lithium battery rises to the point of fire, there will be an unpleasant smell and small smoke. A sensor for monitoring PM2.5/PM10, TVOC, CO air quality is placed on each shelf. When PM2.5/PM10, TVOCS, CO are abnormally elevated, an alarm will be issued.

 

Product Description

 

   Temperature data collector (HY-DTU-002)

         Function

             HY-DTU-002 is an analog temperature collector, which integrates network port, RS485, analog temperature acquisition interface, and 2G/3G/4G mobile network module.

 

温度数据采集器(HY-DTU-002)

 

Parameter Describe
Master Master Industrial Grade Cpu, Main Frequency 540mhz
Memory

64M Byte

FLASH

32M Byte

无线

2G/3G/4G

FDD-LTE,TDD-LTE,DC-HSPA+/HSPA+/HSPA/WCDMA,TD-SCDMA/GSM/GPRS/EDGE

LORA

430~434MHZ, others can be customized 913~918MHz
Sub 1G(customized) 430~434MHZ, others can be customized 866~918MHz
External Interface Data Interface 24 analog temperature interfaces
Supply Voltage DC 12V~36V input
Working Environment Working temperature -10℃~75℃, humidity 0%~90%RH
Current Consumption Working current: <200mA/24V, Maximum current: 1000mA/24V
Software Agreement Operating System

LINUX 3.4

Network Protocol

IP,TCP,UDP,HTTP,HTTPS

Wireless Protocol LORA, Ad Hoc LORA Protocol

RS485

MOBUS, custom 485 communication protocol

 

 

     Air Quality Monitoring Sensors

             Function

                  It is used to monitor the content of PM2.5/PM10 and TVOC in the environment.

    

        空气质量监测传感器

 

 

       Parameter

Sensor Type Measurement Resolution Measuring Range Measurement Accuracy

TVOC

1ug/m3

0ug/m3~999ug/m3

±10%

PM2.5

1ug/m3

0ug/m3~999ug/m3

±10%

PM10

1ug/m3

0ug/m3~1000ug/m3

±10%

 

 

Project Parameter

Remark

Operating Voltage

12V

 

Working Current

<350MA

 

Preheat Time 5 Minutes

 

Operating Temperature

0℃~50℃

 

Working Humidity 15%rh-80%rh (no Condensation)

 

Service Life

5 Years (in Air)

 

Communication Method

Bluetooth RS485,LORA,CAT1 can be customized

Size

φ120mm*42mm (diameter*height)

 

Weight

150mg

 

Installation Method